    北京某城区大型酒店集中空调循环水及淋浴水嗜肺军团菌污染调查

    Investigation on Contamination of Legionella Pneumophila in Recycled Water from Central Air Conditioning Systems and Shower Water in Large Hotels of an Urban District in Beijing

    • 摘要:
      目的 对北京某城区大型酒店集中空调循环水和淋浴水嗜肺军团菌污染现状及卫生管理状况开展调查, 为有效控制军团菌污染提供依据。
      方法 随机抽取北京某城区三星级以上酒店29个, 进行集中空调循环水和淋浴水嗜肺军团菌检测, 并对集中空调循环水系统卫生管理状况进行问卷调查。
      结果 29个酒店有17个检出嗜肺军团菌(58.62%), 冷却水嗜肺军团菌阳性率为40%, 淋浴水阳性率为24.1%;分离的菌株中LP1型占50%, 淋浴水中LP1型占14.3%;三星级、四星级酒店军团菌阳性率均高于五星级酒店; 冷却水军团菌检测频率、机房环境卫生状况都是影响军团菌污染状况的因素。
      结论 嗜肺军团菌污染现状不容乐观, 建议卫生行政部门从多方面对集中空调卫生管理进行评估, 有针对性地开展监督监测, 完善立法, 加大处罚力度和培训宣传力度, 降低军团菌污染的隐患。

       

      Abstract:
      Objectives To investigate the contamination of legionella pneumophila (LP) and sanitary administration in recycled water from central air conditioning systems and shower water in large hotels of an urban district in Beijing and to provide scientific basis for controlling legionella contamination efficiently.
      Methods The contamination of LP in the recycled water of central air conditioning systems was detected in 29 three-star and above hotels selected by random sampling in this area and the sanitary administration was investigated by questionnaire survey.
      Results LP was isolated from 17 hotels (58.62%); the positive rate of LP was 40% in cooling water and was 24.1% in shower water. The predominant serum type of isolated strains was LP 1(50%), which was 14.3% in strains isolated from shower water. The positive rate of LP in five-star hotels were lower than that in three-star and four-star hotels. Factors influencing the contamination of legionella were the frequency of legionella detection in cooling water and the sanitation in engine rooms.
      Conclusions The situation of LP contamination was not optimistic. The sanitary administration of central air conditioning system should be evaluated from multiple aspects and the targeted health supervision and monitoring should be strengthened.It is necessary to improve legislation and strengthen punishment as well as training to prevent the outbreak of legionella contamination.

       

    /