杨轶戬, 施洁, 蒋琴琴, 江思力, 石同幸, 冯文如. 广州市新建二次供水设施卫生学验收评价结果分析[J]. 环境卫生学杂志, 2014, 4(4): 380-382, 387.
    引用本文: 杨轶戬, 施洁, 蒋琴琴, 江思力, 石同幸, 冯文如. 广州市新建二次供水设施卫生学验收评价结果分析[J]. 环境卫生学杂志, 2014, 4(4): 380-382, 387.
    Yang Yijian, Shi Jie, Jiang Qinqin, Jiang Sili, Shi Tongxing, Feng Wenru. Hygienic Evaluation on New Secondary Water Supply in Guangzhou[J]. Journal of Environmental Hygiene, 2014, 4(4): 380-382, 387.
    Citation: Yang Yijian, Shi Jie, Jiang Qinqin, Jiang Sili, Shi Tongxing, Feng Wenru. Hygienic Evaluation on New Secondary Water Supply in Guangzhou[J]. Journal of Environmental Hygiene, 2014, 4(4): 380-382, 387.

    广州市新建二次供水设施卫生学验收评价结果分析

    Hygienic Evaluation on New Secondary Water Supply in Guangzhou

    • 摘要:
      目的 对广州市新建二次供水设施进行竣工验收阶段的现场调查和水质检测, 掌握新建二次供水设施的卫生状况, 为本市新建二次供水设施的卫生安全提供相关的技术措施。
      方法 对2013年广州市待竣工验收的新建二次供水设施, 依照《二次供水设施卫生规范》(GB 17051-1997) 进行现场调查, 依照《生活饮用水标准检验方法》(GB/T 5750-2006) 进行水质抽样检测。结果共调查二次供水设施144个, 存在的卫生问题主要是水箱入口加盖未上锁, 水箱顶距屋顶小于80 cm; 抽检二次供水水箱水144份, 合格117份, 合格率为81.3%, 与市政自来水比较差异无统计学意义; 主要不合格的项目是细菌总数、浑浊度和铁, 合格率分别为84.0%、98.6%和98.6%。
      结论 广州市新建二次供水设施和水质存在一些问题, 需要多部门、多阶段参与加强规范建设、卫生管理和监督检测。

       

      Abstract:
      Objectives To investigate and understand the sanitary status of new secondary water supplies in Guangzhou, and provide related technologies and measures for the hygienic safety of drinking water from the new secondary water supplies constructed in Guangzhou in 2013.
      Methods Investigating the new secondary water supplies and testing the quality of water samples according to related national standards and norms.
      Results The main hygienic defects in 144 new secondary water supplies investigated were not locking the entrance of water tank, and too close of water tank to the ceiling of room. The quality of 144 water samples in 117 tested water samples was good and the qualified rate was 81.3%. There was no significant difference on the qualified rate between the secondary water and the terminal water in the city (P>0.05). The major unqualified items were total bacterial counts, turbidity and iron, and their qualified rates were 84.0%, 98.6% and 98.6%, respectively.
      Conclusions There were some hygienic problems on new secondary water supplies in Guangzhou. Strengthening a participation of multi-department and multi-stage cooperation to construct standard hygienic management, supervision and inspection is needed.

       

    /