2025年上海市浦东新区室内公共游泳场所空气微生物污染状况分析

    Analysis of air contamination with microorganisms in indoor public swimming venues in Pudong New Area, Shanghai, 2025

    • 摘要:
      目的 了解上海浦东新区室内公共游泳场所空气微生物污染水平并分析其影响因素。
      方法 于2025年7—9月对上海市浦东新区26家室内公共游泳场所开展调查, 检测空气温度、相对湿度、细菌总数、集中空调通风系统送风中细菌总数和真菌总数五项指标。采用Mann-Whitney U检验分组比较微生物指标差异; 采用Spearman秩相关分析法分析微生物指标的影响因素。
      结果 所调查26家室内公共游泳场所室内空气温度、相对湿度、细菌总数、集中空调通风系统送风中的细菌总数和真菌总数M(P25, P75)分别为29.6(29.4, 29.8)℃、70.7%(70.1%, 71.5%)、2.0(1.0, 5.0)个/皿、304.0(156.5, 440.3)CFU/m3和218.5 (140.0, 328.5)CFU/m3; 主营游泳场所送风中的细菌总数(M=327.0 CFU/m3)和真菌总数(M=263.0 CFU/m3)均高于兼营游泳场所(M分别为191.5和192.5 CFU/m3)(Z值分别为-2.92和-2.72, P<0.05)。儿童游泳场所送风中的细菌总数(M=561.0 CFU/m3)水平高于成人游泳场所(M=269.0 CFU/m3)(Z=-3.16, P<0.01);中小型游泳场所送风中的细菌总数(M=439.0 CFU/m3)和真菌总数(M=269.0 CFU/m3)水平高于大型游泳场所(M分别为230.0和198.0 CFU/m3)(Z值分别为-4.08和-2.19, P<0.05)。影响因素方面, 空气细菌总数与相对湿度存在负相关(rs=-0.223, P<0.05), 空气细菌总数与送风中细菌总数呈正相关(rs=0.388, P<0.01);送风中细菌总数与温度、送风中真菌总数呈正相关(rs=0.259, P<0.05;rs=0.420, P<0.01)。
      结论 集中空调通风系统的送风可能是2025年夏季上海市浦东新区室内公共游泳场所空气细菌的来源之一。主营游泳场所、儿童游泳场所和中小型游泳场所空气微生物污染风险相对较高。

       

      Abstract:
      Objective To investigate the levels of air contamination with microorganisms in indoor public swimming venues in Pudong New Area, Shanghai, and identify the influencing factors.
      Methods From July to September 2025, a survey was conducted at 26 indoor public swimming venues in Pudong New Area, Shanghai. Five indicators were measured, including air temperature, relative humidity, total bacterial count, and total bacterial and fungal counts in the supply air of central air conditioning ventilation systems. The Mann-Whitney U test was used to compare the differences in microbial indicators between groups. Spearman's rank correlation analysis was employed to identify the influencing factors of microbial indicators.
      Results The M(P25, P75) of the indoor air temperature, relative humidity, total air bacterial count, total bacterial count in the supply air, and total fungal count in the supply air of the 26 investigated indoor public swimming venues were 29.6 (29.4, 29.8) ℃, 70.7% (70.1%, 71.5%), 2.0 (1.0, 5.0)CFU/plate, 304.0 (156.5, 440.3)CFU/m3, and 218.5 (140.0, 328.5)CFU/m3, respectively. The total bacterial count (M=327.0 CFU/m3) and total fungal count (M=263.0 CFU/m3) in the supply air of dedicated swimming venues were higher than those of multi-functional swimming venues (M=191.5 CFU/m3, 192.5 CFU/m3) (Z=-2.92, -2.72; both P < 0.05). The total bacterial count in the supply air of children's swimming venues (M=561.0 CFU/m3) was higher than that of adult swimming venues (M=269.0 CFU/m3) (Z=-3.16, P < 0.01). The total bacterial count (M=439.0 CFU/m3) and total fungal count (M=269.0 CFU/m3) in the supply air of medium- and small-sized swimming venues were higher than those of large-sized swimming venues (M=230.0 CFU/m3, 198.0 CFU/m3) (Z=-4.08, -2.19; both P < 0.05). In terms of influencing factors, there was a negative correlation between the total air bacterial count and relative humidity (rs=-0.223, P < 0.05), and a positive correlation between the total air bacterial count and the total bacterial count in the supply air (rs=0.388, P < 0.01). Additionally, the total bacterial count in the supply air was positively correlated with air temperature and the total fungal count in the supply air (rs=0.259, P < 0.05; rs=0.420, P < 0.01).
      Conclusion The supply air of central air conditioning ventilation systems may be one of the sources of bacteria in the air of indoor public swimming venues in Pudong New Area, Shanghai, in the summer of 2025. Dedicated swimming venues, children's swimming venues, and medium- and small-sized swimming venues have relatively high risks of air contamination with microorganisms.

       

    /